Building Regulations Amendments to Approved Documents B
Published on 19 July 2007 at 20:44
The most obvious change to the Approved Document is that it is
now produced in two volumes. Volume 1 “Dwellinghouses” and Volume
2 “Buildings other than dwellinghouses”. Both documents follow
the same format and layout as the 2000/2002 edition.
Changes in Volume 2 Buildings other than
dwellinghouses.
-
An option of providing sprinkler protection instead of an
alternative route in flats with more than one storey.
-
New guidance on the design of residential care homes given
including the use of sprinklers.
-
Sprinkler systems should be provided in blocks of flats
exceeding 30m.
-
The predicted deflection of a floor in a fire should be
accommodated in the design of a compartment wall.
-
A maximum compartment size has been introduced for
unsprinklered warehouses.
-
Extensive voids under floor should be subdivided with cavity
barriers.
-
Where buildings are on the same site but operated by different
organisations then space separation will apply.
-
Assembly buildings with a floor exceeding 900m 2 at 7.5m or
more will need firefighting shafts.
-
In unsprinklered buildings over 18m every part of every
building should be within 45m of a fire main outlet.
-
Fire mains should be designed according to the provisions of
BS 9990:2006 Code of practice for non-automatic fire
fighting systems in buildings.